...Hunt TNS steam boilers ...

TNS Horizontal Steam Boilers...

The TNS range of horizontal steam boilers feature a three pass reverse flame system incorporated into a wet back style firetube.

They are manufactured in our Hunt Boilers' Victorian workshops and configured for unattended operation up to 500 kW, and limited attendance operation for the balance of the product range.

With significant success in the market place, the TNS is noted for its ability to withstand a wide variation in water quality and excellent steam load balancing capabilities.

The key features of the product range include:

Three pass gas circulation

No refractories: wet back principle

Low maintenance

High thermal efficiency

Large steam chamber to meet fluctuating demands

Complete water space around furnace

Fully packaged complete with feed water pump(s)

Low operating noise levels

Water level probes fitted directly into boiler drum

High class finish and appearance

Colorbond® external cladding

Higher pressure models also available

 

Standard Product Specifications
Model
Capacity
Evaporation
Working Pressure
Feedwater In
Safety Valve
Blowdown
Steam
Main Dimensions
Dry Weight
Get Boiler
FACT SHEET
kW
from & @ 100dC kgs/hr
kPa
p.s.i.
mm
mm
mm
mm
(L x W x H) mm
kgs
TNS200
200
320
700
101
20
20
25
25
2390 x 1250 x 1405
1200
TNS300
300
480
700
101
25
20
25
32
3036 x 1250 x 1613
1550
TNS400
400
640
700
101
25
25
40
50
3067 x 1250 x 1613
1600
TNS500
500
800
700
101
25
25
40
50
3250 x 1650 x 1957
2850
TNS630
630
1000
700
101
25
32
40
65
3310 x 1920 x 2000
2100
TNS750
750
1190
700
101
25
32
40
65
3662 x 2070 x 2150
2400
TNS800
800
1270
700
101
25
40
40
65
3795 x 1980 x 2100
2500
TNS940
940
1500
700
101
25
40
40
65
3662 x 2250 x 2210
2600
TNS1255
1255
2000
700
101
25
50
40
65
3810 x 2260 x 2470
3500
TNS1567
1567
2500
700
101
25
50
40
80
4190 x 2260 x 2470
7500
TNS1880
1880
3000
700
101
25
50
40
80
4320 x 2400 x 2580
8500